How Do You Troubleshoot Using Supervision Voltage?

Go to the Home Page of Douglas Krantz - Engineering Technician


Measure Supervision Voltage before pressing reset or disabling any zones to find out what is happening in the circuit
To find out what's happening in the field, measuring Supervision Voltage at the panel can tell the technician whether it's a normal circuit (same voltage as a normal zone), an open wire (higher voltage than normal), water on the wires or smoke detector in alarm (lower voltage than normal), or a shorting device like a pull station or heat detector, or even a wire-to-wire short (zero or near zero voltage).
This website uses cookies.
See Privacy for details.

By Douglas Krantz

Troubleshooting is like fishing; patience is the key, but not too much patience. If using one method, the fish is caught, go for it. But, if after a while no fish, change methods or you're wasting time.

It's the same with troubleshooting. If, using one method of troubleshooting you find the problem, go for it. But if the problem remains elusive, change troubleshooting methods.


Supervision Voltage Method

With Fire Alarm Systems, one method of troubleshooting is measuring supervision voltage. It's the voltage at the panel's IDC input terminals (Initiating Device Circuit for conventional detectors, pull stations, waterflow switches, etc.) or NAC output terminals (Notification Appliance Circuit for the horns, strobes, speakers, etc.).

Supervision voltage is generated by the fire alarm panel. When the fire panel is looking for trouble on the system, the panel uses the supervision to determine, among other things, whether the wires are still connected.

Using supervision voltage, the panel:
  • Supervises the wiring, making sure the wires and connections remain good at all times, in either Class B or Class A wiring systems
  • Powers the detectors
  • Detects if a switch is closed or a detector is in alarm
Supervision voltages can be:
  • Near zero volts
  • Low
  • Normal
  • High

Supervision Voltage Measurements

Normally the supervision voltage is lower than the open circuit voltage, but higher than the alarm or short circuit voltage.

For troubleshooting, one can use the manufacturer's maintenance manual to find out the normal supervision voltage. This is ideal, but most of us aren't so fortunate as to have this documentation with us while troubleshooting a system that has been in place for several years.

Instead, after checking the panel to see what zone is off-normal, make a comparison of the voltage between a normal zone and the zone in trouble or alarm.

I receive commissions for purchases made through links in this post

Supervision Voltage Equaling Zero

On the off-normal zone, near zero volts indicates a pull/flow/heat detector/gatevalve switch in alarm, or the wires are shorted. Usually it's a switch in alarm.

Check what's on the zone. Spending a little time walking around the building and looking for the pull station in alarm or gatevalve off normal may save a lot of time troubleshooting.

One time I was outside a building in the parking lot when the alarms sounded. I waited for the fire department to arrive and entered the building with them. They didn't find anything, so they started to leave.

But, by checking the supervision voltage, I found a waterflow switch zone still showing zero volts, meaning meant water was flowing somewhere.

I then called the fire department back into the building. It wasn't until after they came back inside that they saw water flowing out of an unoccupied apartment in the basement.

Supervision Voltage Low

On the other hand, if the voltage is a little low to moderately low, the trouble may be a smoke detector in alarm.

One time, in a brightly lit stairwell, a smoke detector in alarm was missed by the fire department because the LED was washed out by sunlight.

Then again, the lower voltage may be water on the line, partially shorting the circuit.

More than once, letting the water out of the junction box has fixed that problem.

Supervision Voltage Normal

If the supervision voltage is the same as other zones, go on to using another method of troubleshooting.

Supervision Voltage High

If the voltage is higher than normal, then it's more likely an open circuit.


Supervision Voltage

Reading the supervision voltage on the zone having problems and seeing whether it is too high, normal, too low, or near zero helps narrow down what to look for and where to look.

But, as I said at the start, this is just one method of troubleshooting. If reading supervision voltage doesn't help, go on to look for the fire alarm system problem using a different method of troubleshooting.


More Articles

What's the Difference Between Class A and Class B? -- The Fire Alarm System is a Life Safety System - so the occupants of a building can escape quickly, the idea behind a Fire Alarm System is that it will provide a warning that there is a fire. The trouble is, if something is wrong with the system, like a wire is broken somewhere in the building, the Fire Alarm System... Read More

What is Fire Alarm Class B Wiring? -- Fire alarm people are paranoid. They're afraid everything is working against them. They're in fear that that if anything goes wrong... Read More

Why is Supervised Wiring So Important? -- Based on Life Safety considerations, supervision makes the difference between building low voltage wiring and building fire alarm system wiring... Read More

How Does Class A Fire Alarm Wiring Work?-- Fire alarm systems save lives and protect property. Fire alarm systems also break down because... Read More




 Get your free diagram showing supervision for Class B wiring

Douglas Krantz -- Fire Alarm Engineering Technician, Electronic Designer, Electronic Technician, Writer

Go to the Writer Home Page of Douglas Krantz -- Describing How It Works
Go to the Fire Alarm Operation Map Page of Douglas Krantz - Technical Writer
Go to the General Electrical Map Page of Douglas Krantz - Technical Writer
Go to the Fire Alarm Description Map Page of Douglas Krantz - Technical Writer
Go to the Fire Alarm Installing Map Page of Douglas Krantz - Technical Writer
Go to the Fire Alarm Maintaining Map Page of Douglas Krantz - Technical Writer
Go to the Fire Alarm Testing Map Page of Douglas Krantz - Technical Writer
Go to the Fire Suppression Map Page of Douglas Krantz - Technical Writer