Can More Than One Class A Circuit be in a Conduit?

Signed J N

Answer

How many Class A Circuits are in a single conduit isn't really the issue. The issue is separating the feed part of any Class A Circuit from the return part of the same circuit.

Keep in mind the purpose of Class A isn't so any problem with the wiring can be repaired in a timely manner; the purpose of Class A is to keep the system working before any wiring problems can be repaired - especially if something breaks once the fire hits and starts to degrade the system.

With Class A, like beads on a necklace, all of the devices are daisy chained on the circuit. The panel is where the feed part of daisy chain starts, and the panel is where the return part of the daisy chain ends. This way, both ends of the daisy chain are attached to the panel.

If the daisy chain is broken somewhere in the middle, the panel is still connected to both ends of the daisy chain. The idea is that signals can get to the panel either on the feed side of the daisy chain or the return side.

The feed and return from devices should be separate so whatever breaks one part of the circuit won't be breaking both the feed side of the daisy chain and the return side for any device.

The biggest concern is survivability of a Class A Circuit (in case a wire breaks, can the panel still communicate with the devices). Just keep the feed and return separate, and the rest can be just standard fire alarm wiring practices.

Douglas Krantz


More Articles

What Makes the End of Line Resistor So Important? -- To allow the panel's internal ohmmeter to check the continuity of the wires (supervise the wires), the end-of-line resistor is at the end of the loop: the last device.Read More

How is an End of Line Resistor a Pull-Down Resistor? -- Sometimes when troubleshooting, the technician has to think inside the box. For instance, take... Read More

What is Fire Alarm Class B Wiring? -- Fire alarm people are paranoid. They're afraid everything is working against them. They're in fear that that if anything goes wrong... Read More

Why Use Pigtails or a UL Approved End-of-Line Resistor? -- Many times, a fire alarm system installer will put the leads of an end-of-line resistor... Read More

Post this by your fire alarm panel -- It shows the in-house fire alarm system and how it calls the fire department.


Want New Articles
Twice a Month?
Join Short Circuit


Go to the Writer Home Page of Douglas Krantz -- Describing How It Works
Go to the Fire Alarm Operation Map Page of Douglas Krantz - Technical Writer
Go to the General Electrical Map Page of Douglas Krantz - Technical Writer
Go to the Fire Alarm Description Map Page of Douglas Krantz - Technical Writer
Go to the Fire Alarm Installing Map Page of Douglas Krantz - Technical Writer
Go to the Fire Alarm Maintaining Map Page of Douglas Krantz - Technical Writer
Go to the Fire Alarm Testing Map Page of Douglas Krantz - Technical Writer
Go to the Fire Suppression Map Page of Douglas Krantz - Technical Writer





Advertisement